Analysis of effect of design water temperature for essential service water system on thermal design of cold chain heat exchanger

  • 1. State Key Laboratory of Nuclear Power Safety Monitoring Technology and Equipment, China Nuclear Power Engineering Co. Ltd., Shenzhen, Guangdong (China)

Description

The design water temperature (TSEC) of essential service water system is an important parameter affecting the thermal design of the cold chain heat exchanger. With the increasing of TSEC, the thermal design conditions of the cold chain heat exchanger tend to be bad, resulting in a gradual increasing in heat exchange area and equipment size. This paper takes the typical thermal design condition of the cold chain heat exchanger as the design input. For the different TSEC, the thermal hybrid design method is adopted to obtain the plate solutions of the cold chain heat exchanger. The number of total channels of the cold chain heat exchanger, the proportion of channels, and the total heat transfer coefficient with TSEC are analyzed. It was found that for specific thermal design conditions, the cold chain heat exchanger can only achieve a perfect match of pressure drop and heat transfer margin within a certain TSEC range, and there is a critical temperature. When TSEC is higher than this temperature, the number of plates will increase rapidly, and TSEC should be avoided as much as possible above this critical temperature. (authors)

Additional details

Identifiers

Publishing Information

Journal Title
Nuclear Power Engineering
Journal Volume
41
Journal Issue
1
Journal Page Range
p. 108-112
ISSN
0258-0926

Optional Information

Notes
2 figs., 4 tabs., 3 refs.; http://dx.doi.org/10.13832/j.jnpe.2020.01.0108