Published August 2013
| Version v1
Journal article
Analysis of high on-line vibration measurement of nuclear power half-speed turbo-generator
Creators
- 1. Daya Bay Nuclear Power Operation and Management Co., Ltd., Shenzhen (China)
Description
Aiming at the problem of the high on-line vibration of the nuclear power half-speed turbo-generator, this paper made a step-by-step analysis according to the vibration spectrum, off-line vibration test, electromagnetic interference verification, and natural frequency knock test. Finally a conclusion was made that the natural frequency of the sensor support setting is close to the four times harmonic wave of the generator operating frequency, resulting in sensor support setting resonance, which is the key reason of the high on-line vibration measurement. (authors)
Additional details
Publishing Information
- Journal Title
- Nuclear Power Engineering
- Journal Volume
- 34
- Journal Issue
- 4
- Journal Page Range
- p. 136-139
- ISSN
- 0258-0926
INIS
- Country of Publication
- China
- Country of Input or Organization
- China
- INIS RN
- 47112337
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- ELECTRIC GENERATORS; MEASURING METHODS; MECHANICAL VIBRATIONS; NUCLEAR POWER PLANTS; SENSORS; SUPPORTS
- Descriptors DEC
- ELECTRICAL EQUIPMENT; EQUIPMENT; MECHANICAL STRUCTURES; NUCLEAR FACILITIES; POWER PLANTS; THERMAL POWER PLANTS
Optional Information
- Notes
- 7 figs., 1 tab., 3 refs.