Environmental effects of mechanical draft cooling tower operations associated with gaseous diffusion plants are discussed. Four studies at the Oak Ridge Gaseous Diffusion Plant towers which dissipate a heat load equivalent of 100 megawatts electrical are summarized. Total drift, air concentration, and deposition patterns are determined. Transfer of drift to the environment is studied. Measured field data is compared with a theoretical model for cooling tower drift. Chromium and zinc content of cooling tower drift and the associated environment including plants, soil, and air is determined