Ampacity test of a silicone foam firestop in a cable tray
Description
An ampacity (current loading) test was conducted on 600 volt cables in open top cable trays in a controlled atmosphere. The cable trays were placed in a simulated nuclear plant wall penetration with a silicone foam firestop. The purpose of the test was to determine whether the penetration and firestop would cause the conductor temperatures to exceed the temperature ratings of the insulation of the cables used at Fermi 2. Test results showed that the temperatures attained were not excessive, and that the IPCEA (Insulated Power Cable Engineers Association-National Electrical Manufacturers Association; IPCEA is now ICEA) Tables from which the conductors were selected may be conservative
Additional details
Publishing Information
- Publisher
- Institute of Electrical and Electronics Engineers.
- Imprint Place
- Piscataway, NJ
- Imprint Title
- IEEE Power Engineering Society summer meeting
- Journal Page Range
- p. vp.
Conference
- Title
- IEEE Power Engineering Society summer meeting.
- Dates
- 26 - 31 Jul 1981.
- Place
- Portland, OR (USA).
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 14724227
- Subject category
- S61: RADIATION PROTECTION AND DOSIMETRY;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- ELECTRIC CABLES; ELECTRICAL TESTING; FIRES; NUCLEAR POWER PLANTS; REACTOR SAFETY; SILICONES
- Descriptors DEC
- CABLES; CONDUCTOR DEVICES; ELECTRICAL EQUIPMENT; EQUIPMENT; MATERIALS TESTING; NONDESTRUCTIVE TESTING; NUCLEAR FACILITIES; POLYMERS; POWER PLANTS; SAFETY; SILOXANES; TESTING; THERMAL POWER PLANTS