Summary report of incineration plenum fire: Building 771, July 2, 1980

Description

At about 1100 on July 2, 1980, a temperature rise above normal was recorded on charts monitoring operation of the incinerator in Room 149, Building 771. The plenum overheat alarm sounded at 1215, emergency actions initiated, and the fire was extinguished and mop-up began at about 1300. Investigation determined that the fire in the plenum was caused by a heat rise in the system, a deteriorated bypass valve on the No. 3 heat exchanger (KOH scrubber), nitration of the urethane seal on the HEPA filter media to the filter frame, and accumulation of metallic fines on the filter media. It was concluded that the management system responded properly, except for the ring- down system to activate the Emergency Operations Center

Availability note (English)

MF available from INIS under the Report Number; Also available from OSTI as DE95014665; NTIS; US Govt. Printing Office Dep.

Files

26077278.pdf

Files (2.7 MB)

Name Size Download all
md5:a495947236491a8245423d0ce2b846bd
2.7 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
41 p.
Report number
RFP--4969

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
26077278
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Descriptors DEI
EMERGENCY PLANS; FIRES; INCINERATORS; ROCKY FLATS PLANT
Descriptors DEC
NATIONAL ORGANIZATIONS; US AEC; US DOE; US ERDA; US ORGANIZATIONS

Optional Information

Contract/Grant/Project number
Contract AC34-90RF62349
Funding organization
USDOE, Washington, DC (United States).