Published November 1985 | Version v1
Report Open

Possible options for reducing occupational dose from the TMI-2 basement

Description

The major sources of exposure in the basement include the enclosed stairwell/elevator shaft structure, water and sludge in the elevator shaft, cast concrete walls, concrete floor slab, water and sludge on the floor, and activity in the paint and loose surface contamination. The sources were identified using data obtained by the utility from water processing, water and solid samples, remote video inspections and radiation monitoring with a robot, and strings of thermoluminescent dosimeters lowered from upper elevations. The area dose rates in the basement range from approximately 4 R/hr (in the NE quadrant) to over 1100 R/hr (near the enclosed stairwell/elevator shaft structure). It is estimated that the basement contains between 11,000 and 21,000 curies of 137Cs. Specific decontamination and cleanup techniques are discussed. These techniques include flushing with water, high-pressure water blasting, leaching, scabbling and chemical cleaning. The applicability of these techniques to the major sources of radiation are discussed, and possible approaches and work sequences for basement cleanup are given

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS, PC A06/MF A01 - GPO as TI86003775.

Files

17036681.pdf

Files (7.2 MB)

Name Size Download all
md5:e93438006efa6d4a6a6dcd36b02951a7
7.2 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
119 p.
Report number
NUREG/CR--4399

Optional Information

Secondary number(s)
PNL--5557.