Published May 1989 | Version v1
Report

Effects of temperature and humidity on the aging of TEDA impregnated charcoals

  • 1. Central Electricity Generating Board, Surrey (England)

Description

Samples of triethylene diamine (TEDA) impregnated 207B carbon have been aged for up to 1000 hours at temperatures in the range 40 degree to 70 degree c and at relative humidities of 50% and 90%. The rate of aging (in terms of methyl iodide-131 trapping efficiency) increases progressively as the temperature is raised above 50 degree C and also as the relative humidity is increased; below 50 degree C however the aging rate is relatively low, even at 90% RH. A parallel examination by temperature programmed desorption of the growth of surface oxygen groups with aging indicates that, unlike KI impregnated carbons, the groups formed on the TEDA carbons are not linked to the decline in performance. Also, the presence of an amine, which, as a group, are generally regarded as anti-oxidants, does not reduce the rate of surface oxidation. The rate of aging of TEDA carbons has been shown to follow the increase in the partial pressure of water above the sample and it is proposed that TEDA carbon aging could be caused by loss of TEDA either by a process akin to steam distillation, or by reaction with or catalysis by water, to form a less efficient impregnant

Additional details

Publishing Information

Imprint Title
Proceedings of the 20th DOE/NRC nuclear air cleaning conference. Sessions 1--5
Imprint Pagination
627 p.
Journal Page Range
p. 572-588.
Report number
NUREG/CP--0098-Vol.1

Conference

Title
20. DOE/NRC nuclear air cleaning conference.
Dates
22-25 Aug 1988.
Place
Boston, MA (USA).

Optional Information

Secondary number(s)
CONF-880815--Vol.1.