Published 2009
| Version v1
Miscellaneous
Darlington NGS vacuum building outage: modification to supply post-seismic makeup water to the heat transport system
Description
The periodic stationwide outage at Darlington NGS includes removal of the Emergency Coolant Injection System from service to allow for maintenance. As a prerequisite, the station must set up a minimum 2.5 kg/s temporary makeup water supply, to help cool the fuel should a seismic event occur. This modification cannot be commissioned, as commissioning would dilute the heavy water in the Primary Heat Transport System with light water. Therefore, flow analysis is necessary to demonstrate that the required flow rate can be achieved. This paper provides details of the design, and key aspects of the supporting analysis. (author)
Availability note (English)
Also available as a slide show presentationAdditional details
Publishing Information
- Publisher
- Canadian Nuclear Society
- Imprint Place
- Toronto, Ontario (Canada)
- ISBN
- 0-919784-95-X
- Imprint Title
- New nuclear frontiers. 30th annual Canadian Nuclear Society conference and 33rd CNS/CNA student conference
- Imprint Pagination
- 275 Megabytes
- Journal Page Range
- [11 p.]
Conference
- Title
- 30. annual canadian nuclear society conference; 33. CNS/CNA student conference
- Dates
- 31 May - 3 Jun 2009
- Place
- Calgary, Alberta (Canada)
INIS
- Country of Publication
- Canada
- Country of Input or Organization
- Canada
- INIS RN
- 41007174
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- DARLINGTON SITE; ECCS; OUTAGES; PRIMARY COOLANT CIRCUITS; REACTOR COOLING SYSTEMS
- Descriptors DEC
- COOLING SYSTEMS; ENERGY SYSTEMS; ENGINEERED SAFETY SYSTEMS; REACTOR COMPONENTS; REACTOR COOLING SYSTEMS; REACTOR PROTECTION SYSTEMS; REACTOR SITES
Optional Information
- Notes
- 8 refs., 1 tab., 6 figs.