Published February 1984
| Version v1
Journal article
Test results of the cooling tower with the capacity of 100000 m3/h
Creators
Description
Unique cooling towers with the capacity of 100000 m3/h have been used for the first time in power generation practice of the USSR as colers for the Rovno NPP circulation water supply. During tests in the summer-autumn, period of 1981 the thermohydraulic characteristics of such a tower were determined. The tests have shown that the tower has a high cooling efficiency in a wide range of thermal and hydraulic loadings. Deviation of actual temperatures of cooled water in the tower from their value, found according to nomograms, has not exceeded +-1.0 deg C
Additional details
Additional titles
- Original title (Russian)
- Результаты испытаний башенной градирни производительностью 100 тыс. м
Publishing Information
- Journal Title
- Ehlektr. Stn.
- Journal Issue
- no.2
- Series
- Ehlektr. Stn.
- ISSN
- 0013-5372
INIS
- Country of Publication
- Russian Federation
- Country of Input or Organization
- USSR
- INIS RN
- 16006932
- Subject category
- S22: GENERAL STUDIES OF NUCLEAR REACTORS; S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- COOLING TOWERS; FLUX DENSITY; HEAT FLUX; MEDIUM TEMPERATURE; NOMOGRAMS; PERFORMANCE TESTING; TEMPERATURE DEPENDENCE; THERMAL EFFICIENCY; WIND; WWER TYPE REACTORS
- Descriptors DEC
- DIAGRAMS; EFFICIENCY; ENRICHED URANIUM REACTORS; INFORMATION; POWER REACTORS; PWR TYPE REACTORS; REACTORS; TESTING; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS
Optional Information
- Notes
- For English translation see the journal Soviet Power Engineering (English Translation).