Published February 1984 | Version v1
Journal article

Test results of the cooling tower with the capacity of 100000 m3/h

Description

Unique cooling towers with the capacity of 100000 m3/h have been used for the first time in power generation practice of the USSR as colers for the Rovno NPP circulation water supply. During tests in the summer-autumn, period of 1981 the thermohydraulic characteristics of such a tower were determined. The tests have shown that the tower has a high cooling efficiency in a wide range of thermal and hydraulic loadings. Deviation of actual temperatures of cooled water in the tower from their value, found according to nomograms, has not exceeded +-1.0 deg C

Additional details

Additional titles

Original title (Russian)
Результаты испытаний башенной градирни производительностью 100 тыс. м

Publishing Information

Journal Title
Ehlektr. Stn.
Journal Issue
no.2
Series
Ehlektr. Stn.
ISSN
0013-5372

Optional Information

Notes
For English translation see the journal Soviet Power Engineering (English Translation).