Trapped air and the onset of cavitation in piping systems

  • 1. Vermont Yankee Nuclear Power Corp., Rutland, VT (United States)

Description

Repetitive Reactor Water Clean Up (RWCU) pump trips were experienced at VYNPC, particularly during reactor cooldown to shutdown conditions. A study of various RWCU trips occurred over the last 10 years established that, for cases where no system isolation signal or known pump trip signals existed, the pump trips were caused by system low flow linked to cavitation induced flow oscillations. However, theoretical relationships at pump inlet indicated a reasonable margin to maximum allowable flow to prevent cavitation. It was then determined that air was present in solution in the form of either dispersed air or large pockets. Air pockets at system high points could move to the pump inlet causing low suction pressure and subsequent system low flow while small air bubbles distributed in the fluid impact the pressure of vaporization, creating better conditions for the onset of cavitation. This paper discusses the implications of air entrapped in piping systems and provides some recommendations to restore margin to cavitation conditions. (author)

Availability note (English)

Available from INIS in electronic form

Files

33007987.pdf

Files (29.0 kB)

Name Size Download all
md5:78e4e4791872f3623b91b9a374000585
29.0 kB Preview Download

Additional details

Publishing Information

Imprint Pagination
[1 p.]
Report number
INIS-FR--625

Conference

Title
9. international conference on nuclear engineering
Dates
8-12 Apr 2001
Place
Nice, Acropolis (France)

INIS

Country of Publication
France
Country of Input or Organization
France
INIS RN
33007987
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
AIR; CAVITATION; FLUID FLOW; OSCILLATIONS; PIPES; PUMPS; REACTOR COMPONENTS; REACTOR SHUTDOWN
Descriptors DEC
EQUIPMENT; FLUIDS; GASES; SHUTDOWN; TUBES