Flow meter fault isolation in building central chilling systems using wavelet analysis
- 1. College of Civil Engineering, Hunan University, Changsha, Hunan 410082 (China)and School of Mechanical and Aerospace Engineering, Oklahoma State University, Stillwater, OK 74078-5016 (United States)
- 2. College of Energy and Safety Engineering, Hunan University of Science and Technology, Xiangtan, Hunan 411201 (China)
- 3. College of Civil Engineering, Hunan University, Changsha, Hunan 410082 (China)
- 4. Department of Building Services Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong (China)
Description
This paper presents an approach to isolate flow meter faults in building central chilling systems. It mathematically explains the fault collinearity among the flow meters in central chilling systems and points out that the sensor validation index (SVI) used in principal component analysis (PCA) is incapable of isolating flow meter faults due to the fault collinearity. The wavelet transform is used to isolate the flow meter faults as a substitute for the SVI of PCA. This approach can identify various variations in measuring signals, such as ramp, step, discontinuity etc., due to the good property of the wavelet in local time-frequency. Some examples are given to demonstrate its ability of fault isolation for the flow meters
Additional details
Identifiers
- DOI
- 10.1016/j.enconman.2005.10.023;
- PII
- S0196-8904(05)00273-6;
Publishing Information
- Journal Title
- Energy Conversion and Management
- Journal Volume
- 47
- Journal Issue
- 13-14
- Journal Page Range
- p. 1700-1710
- ISSN
- 0196-8904
- CODEN
- ECMADL
INIS
- Country of Publication
- United Kingdom
- Country of Input or Organization
- International Atomic Energy Agency (IAEA)
- INIS RN
- 37069282
- Subject category
- S99: GENERAL AND MISCELLANEOUS;
- Descriptors DEI
- BUILDINGS; FLOWMETERS; INDEXES; SIGNALS; VALIDATION; VARIATIONS
- Descriptors DEC
- DOCUMENT TYPES; MEASURING INSTRUMENTS; METERS; TESTING
Optional Information
- Copyright
- Copyright (c) 2005 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.