Published 1994 | Version v1
Journal article

Radon mitigation in schools utilising heating, ventilating and air conditioning systems

  • 1. Camroden Associates, Oriskany, NY (United States)
  • 2. Tulsa Univ., OK (United States)
  • 3. Mountain West Technical Associates, Santa Fe, NM (United States)
  • 4. Kansas State Univ., Manhattan, KS (United States)

Description

As part of a continuing radon in schools technology development effort, EPA's School Evaluation Team has performed radon mitigation in schools by the method of ventilation/pressurisation control technology. Ventilation rates were increased, at a minimum, to meet the American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) standard, Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1989). This paper presents the results and the preliminary evaluations which led to the team's decision to implement this technology. Factors considered include energy penalties, comfort, indoor air quality (IAQ), building shell tightness, and equipment costs. Cost benefit of heat recovery ventilation was also considered. Earlier results of the SEP team's efforts have indicated a severe ventilation problem within the schools of the United States. Two case studies are presented where HVAC technology was implemented for controlling radon concentrations. One involved the installation of a heat recovery ventilator to depressurise a crawl space and provide ventilation to the classrooms which previously had no mechanical ventilation. The other involved the restoration of a variable air volume system in a two-storey building. The HVAC system's controls were restored and modified to provide a constant building pressure differential to control the entry of radon. Pre-mitigation and post-mitigation indoor air pollutant measurements were taken, including radon, carbon dioxide (CO2), particulates, and bio-aerosols. Long-term monitoring of radon, CO2, building pressure differentials, and indoor/outdoor temperature and relative humidity is presented. (author)

Additional details

Publishing Information

Journal Title
Radiation Protection Dosimetry
Journal Volume
56
Journal Issue
1-4
Journal Page Range
p. 51-54.
ISSN
0144-8420
CODEN
RPDODE

Conference

Title
the scientific basis and practical implications.
Acronym
1. international workshop on indoor radon remedial action
Dates
27 Jun - 2 Jul 1993.
Place
Rimini (Italy).

INIS

Country of Publication
United Kingdom
Country of Input or Organization
United Kingdom
INIS RN
28021188
Subject category
S61: RADIATION PROTECTION AND DOSIMETRY;
Resource subtype / Literary indicator
Conference
Descriptors DEI
AIR CONDITIONING; INDOOR AIR CONTAMINATION; RADIATION MONITORING; RADIATION PROTECTION; RADON; REMEDIAL ACTION; SCHOOL BUILDINGS; VENTILATION SYSTEMS
Descriptors DEC
BUILDINGS; CONTAMINATION; EDUCATIONAL FACILITIES; ELEMENTS; MONITORING; NONMETALS; RARE GASES

Optional Information

Secondary number(s)
EUR--16005-EN.