Published 1990
| Version v1
Miscellaneous
Reliability analysis of the high pressure safety injection system of the NPP Angra II
- 1. NUCLEN, Rio de Janeiro, RJ (Brazil). Dept. de Analise e Projeto de Reator
Description
The realibility of the High Pressure Safety Injection System of Angra 2 is evaluated by means of the fault-tree technique, with the use of the computer program FT-DUAL. The results demonstrate that in case of LOCA the unavailability of the high pressure safety injection function required to mitigate the accident is 3.7E-6. A sensitivity analysis of one isolated train of the high pressure safety injection system was performed for the purpose of identifying which modifications in the conceptual design of the system would increase its reliability in case that were required. The modification introduced led the unavailability of the safety function to 1.7 E-6. (author)
Availability note (English)
Available from the Library of the Comissao Nacional de Energia Nuclear, RJ, Brazil.Additional details
Additional titles
- Original title (Portuguese)
- Analise da confiabilidade do sistema de injecao de seguranca de alta pressao de Angra 2 em caso de LOCA
Publishing Information
- Imprint Pagination
- 9 p.
Conference
- Title
- 3. General Brazilian Congress of Nuclear Energy.
- Dates
- 22-27 Jul 1990.
- Place
- Rio de Janeiro, RJ (Brazil).
INIS
- Country of Publication
- Brazil
- Country of Input or Organization
- Brazil
- INIS RN
- 22016725
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- ANGRA-2 REACTOR; F CODES; FAULT TREE ANALYSIS; HIGH PRESSURE COOLANT INJECTIO; LOSS OF COOLANT; RELIABILITY; SENSITIVITY ANALYSIS
- Descriptors DEC
- ACCIDENTS; COMPUTER CODES; ECCS; ENRICHED URANIUM REACTORS; POWER REACTORS; PWR TYPE REACTORS; REACTOR ACCIDENTS; REACTOR PROTECTION SYSTEMS; REACTORS; SYSTEM FAILURE ANALYSIS; SYSTEMS ANALYSIS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS