Published October 2018 | Version v1
Journal article

Application Status and Maintenance Optimization Analysis of Ventilation System Fire Damper in Nuclear Power Plants

  • 1. Suzhou Nuclear Power Research Institute, Shenzhen (China)

Description

In order to improve the reliability of the fire damper in nuclear power plants, the application status and failure history of fire damper in several nuclear power plants were analyzed in this paper. The failure mechanism and maintenance strategy optimization of different fire dampers are studied by Failure Mode and Effect Analysis (FMEA) method. The results show that the annual inspection of appearance and action is optimized, and the task of regularly changing fuse element and electric mechanism is added, which can effectively reduce the failure rate of fire damper and ensure the safe and stable operation of nuclear power plants. (authors)

Additional details

Identifiers

Publishing Information

Journal Title
Nuclear Power Engineering
Journal Volume
39
Journal Issue
5
Journal Page Range
p. 149-153
ISSN
0258-0926

INIS

Country of Publication
China
Country of Input or Organization
China
INIS RN
54087468
Subject category
S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
Descriptors DEI
FAILURES; FIRES; INSPECTION; MAINTENANCE; NUCLEAR POWER PLANTS; OPERATION; OPTIMIZATION; RELIABILITY; VENTILATION SYSTEMS
Descriptors DEC
NUCLEAR FACILITIES; POWER PLANTS; THERMAL POWER PLANTS

Optional Information

Notes
6 figs., 4 tabs., 5 refs.; http://dx.doi.org/10.13832/j.jnpe.2018.05.0149