Published 1993 | Version v1
Journal article

A comparison of fuzzy logic-PID control strategies for PWR pressurizer control

  • 1. Univ. of Tennessee, Knoxville (United States)

Description

This paper describes the results obtained from a comparison performed between classical proportional-integral-derivative (PID) and fuzzy logic (FL) controlling the pressure in a pressurized water reactor (PWR). The two methodologies have been tested under various transient scenarios, and their performances are evaluated with respect to robustness and on-time response to external stimuli. One of the main concerns in the safe operation of PWR is the pressure control in the primary side of the system. In order to maintain the pressure in a PWR at the desired level, the pressurizer component equipped with sprayers, heaters, and safety relief valves is used. The control strategy in a Westinghouse PWR is implemented with a PID controller that initiates either the electric heaters or the sprayers, depending on the direction of the coolant pressure deviation from the setpoint

Additional details

Publishing Information

Journal Title
Transactions of the American Nuclear Society
Journal Volume
68
Journal Page Range
p. 137-139.
ISSN
0003-018X
CODEN
TANSAO

Conference

Title
American Nuclear Society (ANS) annual meeting.
Dates
20-24 Jun 1993.
Place
San Diego, CA (United States).

Optional Information

Secondary number(s)
CONF-930601--.