Published July 1999 | Version v1
Journal article

A study on the behavior of debris around a sump of a safety injection system

Description

The Regulatory Guide 1.82 recommends an analysis of hydraulic performance for sump of ECCS (Emergency Core Cooling System) when LOCA (loss of coolant accident) occurs in a nuclear power plant. The present study deals with 3-dimensional, unsteady, turbulent and two-phase flow simulation to examine the behavior of mixture of reactor coolant and debris near the floor of containment building in conjunction with appropriate assumptions. The dispersed solid model has been adjusted to the interfacial momentum transfer between reactor coolant and debris. According to the results, the counterclockwise recirculation zone had been formed in the region between sump and connection aisle about 376 second after LOCA occurs. The debris thickness accumulated ona sump screen periodically increases or decreases up to 2000 second, afterwards its peak decreases. (author)

Additional details

Publishing Information

Journal Title
Power Engineering
Journal Volume
10
Journal Issue
1
Journal Page Range
p. 80-89
ISSN
1225-8016

Optional Information

Notes
14 refs., 6 figs.