Basis for Interim Operation for Fuel Supply Shutdown Facility
Creators
Description
This document establishes the Basis for Interim Operation (BIO) for the Fuel Supply Shutdown Facility (FSS) as managed by the 300 Area Deactivation Project (300 ADP) organization in accordance with the requirements of the Project Hanford Management Contract procedure (PHMC) HNF-PRO-700, ''Safety Analysis and Technical Safety Requirements''. A hazard classification (Benecke 2003a) has been prepared for the facility in accordance with DOE-STD-1027-92 resulting in the assignment of Hazard Category 3 for FSS Facility buildings that store N Reactor fuel materials (303-B, 3712, and 3716). All others are designated Industrial buildings. It is concluded that the risks associated with the current and planned operational mode of the FSS Facility (uranium storage, uranium repackaging and shipment, cleanup, and transition activities, etc.) are acceptable. The potential radiological dose and toxicological consequences for a range of credible uranium storage building have been analyzed using Hanford accepted methods. Risk Class designations are summarized for representative events in Table 1.6-1. Mitigation was not considered for any event except the random fire event that exceeds predicted consequences based on existing source and combustible loading because of an inadvertent increase in combustible loading. For that event, a housekeeping program to manage transient combustibles is credited to reduce the probability. An additional administrative control is established to protect assumptions regarding source term by limiting inventories of fuel and combustible materials. Another is established to maintain the criticality safety program. Additional defense-in-depth controls are established to perform fire protection system testing, inspection, and maintenance to ensure predicted availability of those systems, and to maintain the radiological control program. It is also concluded that because an accidental nuclear criticality is not credible based on the low uranium enrichment, the form of the uranium, and the required controls, a Criticality Alarm System (CAS) is not required as allowed by DOE Order 420.1 (DOE 2000)
Availability note (English)
Available from PURL: https://www.osti.gov/servlets/purl/810503-3StMYU/native/Additional details
Identifiers
Publishing Information
- Imprint Pagination
- 99 p.
- Report number
- HNF--10108
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 34041661
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS; S12: MANAGEMENT OF RADIOACTIVE WASTES, AND NON-RADIOACTIVE WASTES FROM NUCLEAR FACILITIES;
- Resource subtype / Literary indicator
- Non-conventional Literature
- Descriptors DEI
- ALARM SYSTEMS; CRITICALITY; FIRE PREVENTION; ISOTOPE SEPARATION; MAINTENANCE; MITIGATION; N-REACTOR; PACKAGING RULES; RADIOACTIVE WASTE MANAGEMENT; RADIOACTIVE WASTE STORAGE; RISK ASSESSMENT; SAFETY; SHUTDOWN; SLIGHTLY ENRICHED URANIUM; SOURCE TERMS
- Descriptors DEC
- ACTINIDES; ELEMENTS; ENRICHED URANIUM; ENRICHED URANIUM REACTORS; GRAPHITE MODERATED REACTORS; ISOTOPE ENRICHED MATERIALS; LAWS; LWGR TYPE REACTORS; MANAGEMENT; MATERIALS; METALS; PLUTONIUM PRODUCTION REACTORS; POWER REACTORS; PRODUCTION REACTORS; RADIOACTIVE WASTE MANAGEMENT; REACTORS; REGULATIONS; SEPARATION PROCESSES; STORAGE; URANIUM; WASTE MANAGEMENT; WASTE STORAGE; WATER COOLED REACTORS
Optional Information
- Contract/Grant/Project number
- EDT--621766; AC--06-96RL13200
- Funding organization
- ENVIRONMENTAL MANAGEMENT (United States)