Published 1992
| Version v1
Miscellaneous
Margin benefit assessment of a digital monitoring system
Creators
- 1. Korea Atomic Energy Research Institute, Taejon (Korea, Republic of)
Description
Quantitative margin benefits are assessed when a Digital Monitoring System (DMS) is installed to an operating Westinghouse type plant. Applied plant and cycle is Yonggwang Unit 1 Cycle 6. The referenced digital monitoring system is the COLSS (Core Operating Limit Supervisory System) of ABB-CE. The most limiting DNB prevention event of CEA Withdrawal is analyzed with the ABB-CE method. The results show that the DMS can bring around 7% more margins for both DNB and LOCA Fq standpoints of view. The DMS can also monitor the PCI limits
Additional details
Publishing Information
- Publisher
- KNS
- Imprint Place
- Taejon (Korea, Republic of)
- Imprint Title
- Proceedings of the KNS autumn meeting
- Imprint Pagination
- 646 p.
- Journal Page Range
- p. 547-552
Conference
- Title
- 1992 autumn meeting of the KNS
- Dates
- 31 Oct 1992
- Place
- Seoul (Korea, Republic of)
INIS
- Country of Publication
- Korea, Republic of
- Country of Input or Organization
- Korea, Republic of
- INIS RN
- 38022738
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- DIGITAL SYSTEMS; LOSS OF COOLANT; MONITORING; WESTINGHOUSE STANDARD REACTOR; YONGGWANG-1 REACTOR
- Descriptors DEC
- ACCIDENTS; ENRICHED URANIUM REACTORS; POWER REACTORS; PWR TYPE REACTORS; REACTOR ACCIDENTS; REACTORS; THERMAL REACTORS; WATER COOLED REACTORS; WATER MODERATED REACTORS
Optional Information
- Notes
- 5 refs, 7 figs, 2 tabs