Published September 1993 | Version v1
Report Open

Idaho Chemical Processing Plant Liquid Effluent Treatment and Disposal Facility hot test report

Description

Prior to initial operation with radioactive feed or ''hot'' operation, the Liquid Effluent Treatment and Disposal (LET ampersand D) Facility underwent extensive testing. This report provides a detailed description and analysis of this testing. Testing has determined that LET ampersand D is capable of processing radioactive solutions between the design flowrates of 275 gph to 550 gph. Modifications made to prevent condensation on the off-gas HEPA filters, to the process vacuum control, bottoms cooler rupture disks, and feed control system operation were successful. Unfortunately, two mixers failed prior to ''hot'' testing due to manufacturer's error which limited operation of the PEW Evaporator System and sampling was not able to prove that design removal efficiencies for Mercury, Cadmium, Plutonium, and Non-Volatile Radionuclides

Availability note (English)

MF available from INIS under the Report Number; Also available from OSTI as DE94008911; NTIS; US Govt. Printing Office Dep.

Files

25059135.pdf

Files (5.4 MB)

Name Size Download all
md5:0a7e9eada6caec513261f0435f06e5d4
5.4 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
128 p.
Report number
WINCO--1146

Optional Information

Contract/Grant/Project number
Contract AC07-84ID12435
Funding organization
USDOE, Washington, DC (United States).