Darlington GS vacuum building - internal structures and foundation

  • 1. Ontario Hydro, Toronto (Canada)

Description

This paper describes the evolution of the internal structure from initial concept to final design. Fundamental changes to the original configuration were precipitated by the action of large seismic forces acting on a top-heavy configuration. Prestressing was eliminated in deference to high humidity. Aspects of the elevated water tank's peripheral support beam are discussed vis-a-vis an adjacent slipforming operation, and practical construction limitations on steel placement. Also reviewed are the shortening of peripheral columns due to shrinkage and creep, and considerations of crack control for purposes of water-tightness. The authors justify the choice of stainless steel for fabrication of the siphon system's riser pipes. The foundation slab must resist the combined effects of vacuum pressure, hydrostatic uplift, and the seismic reactions of the internal structure and perimeter wall. The dependency of a key foundation component, the gallery roof slab, on the dome tendon layout is high-lighted; and aspects of its constructability are reviewed in light of congestion of vertical tendon anchorages, and of reinforcement. The design of the air-tight slab liner is reviewed, attention focusing on weld design under vacuum and accident temperature loads; on corrosion protection; and on the related construction access bulkhead - its ASME requirements and fabrication tolerances. (orig.)

Additional details

Publishing Information

Journal Title
Nucl. Eng. Des.
Journal Volume
85
Journal Issue
2
Series
Nucl. Eng. Des.
Journal Page Range
119-129
ISSN
0029-5493
CODEN
NEDEA