Analysis of Environmental Conditions for NPP Krsko DC Battery and Battery Charger Rooms Following SG Blowdown Processing System Line Break

  • 1. University of Zagreb, Faculty of Electrical Engineering and Computing, Zagreb (Croatia)

Description

This paper describes analysis of thermal-hydraulic conditions in NEK DC Battery and Battery Charger rooms after a postulated break of the SG Blowdown Processing System (SGBD) line. The calculation was performed in frame of Equipment Qualification Parameters determination for NPP Krsko. Such break can result in release of the SG water in NEK Intermediate Building which can endanger the safety related electrical equipment. Since this break cannot happen in the mentioned rooms the presence of HVAC (heating, ventilation and air conditioning) ducts must be taken into account, i.e., the HVAC duct can potentially be damaged under the pressure conditions in the rooms where the SGBD break can occur leaving the free path to the DC Battery and Battery Charger rooms. This analysis covers mass and energy release calculation (MER) due to SG blowdown line break (A), calculation of ventilation duct structural integrity (B), and the pressure and temperature response of selected IB rooms (C). A. The SGBD break is postulated in the Intermediate Building downstream the Containment Isolation valves and upstream of the Blowdown Heat Exchanger to conservatively predict the mass and energy release. This calculation was performed with RELAP5/MOD3.2.2 computer code. B. FEM (Finite Element Method) stress calculation using NISA II and ALGOR computer programs was performed for representative section of the HVAC duct in order to estimate pressure difference which can open the duct and connect battery rooms with the rooms where SG blowdown break was simulated. C. In order to take into account influence of possible damage of HVAC duct on TH conditions in IB rooms 011, 012, 014 and 015 (DC Battery and Battery Charger rooms) the GOTHIC code was used considering SGBD break in rooms IB009 and IB010. (author)

Files

33064283.pdf

Files (26.0 kB)

Name Size Download all
md5:9c63bc433ed71a0c480b6ad52b99a699
26.0 kB Preview Download
Part of:
Book of Abstracts of 4th International Conference: Nuclear Option in Countries with Small and Medium Electricity Grids

Additional details

Publishing Information

Imprint Place
Zagreb (Croatia)
ISBN
953-96132-7-2
Imprint Title
Book of Abstracts of 4th International Conference: Nuclear Option in Countries with Small and Medium Electricity Grids
Imprint Pagination
124 p.
Journal Page Range
p. 46
Report number
INIS-HR--02003

Conference

Title
Nuclear Option in Countries with Small and Medium Electricity Grids
Acronym
4. International Conference
Dates
16-20 Jun 2002
Place
Dubrovnik (Croatia)

Optional Information