Published 2014
| Version v1
Book
Reliability Improvement of JSFR Emergency Power Supply System - 14128
Creators
- 1. Japan Atomic Energy Agency, 4002 Narita, O-arai-machi, Ibaraki-ken, 311-1393 (Japan)
- 2. Mitsubishi FBR systems Inc. (MFBR), 34-17, Jingumae 2-chome, Shibuya-ku, Tokyo 150-0001 (Japan)
Description
One of the advantages in features of Japan Sodium-cooled Fast Reactor (JSFR) is that it's free from high-capacity power load or quick activation of emergency power supply because Decay Heat Removal System (DHRS) adopted natural circulation. However, the Emergency Power Supply System of JSFR is reconsidered to improve the reliability for station blackout (SBO) caused by extreme external events after the nuclear accident at Fukushima. A non-class 1E GTG are added for practically elimination of Loss of Heat Removal System (LOHRS), and alternative power supply system composed of small air-cooled DG and lead-acid batteries is newly introduced to maintain class 1E equipment against the long-term station blackout (SBO). (authors)
Additional details
Publishing Information
- Publisher
- American Nuclear Society - ANS
- Imprint Place
- La Grange Park, IL (United States)
- ISBN
- 978-0-89448-776-7
- Imprint Pagination
- 7 p.
Conference
- Title
- International Congress on Advances in Nuclear Power Plants
- Acronym
- ICAPP 2014
- Dates
- 6-9 Apr 2014
- Place
- Charlotte, NC (United States)
INIS
- Country of Publication
- United States
- Country of Input or Organization
- France
- INIS RN
- 54022515
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- AFTER-HEAT REMOVAL; LEAD-ACID BATTERIES; LOHRS; NATURAL CONVECTION; RADIATION ACCIDENTS; SODIUM COOLED REACTORS; STATION BLACKOUT
- Descriptors DEC
- ACCIDENTS; BEYOND-DESIGN-BASIS ACCIDENTS; CONVECTION; ELECTRIC BATTERIES; ELECTROCHEMICAL CELLS; ENERGY STORAGE SYSTEMS; ENERGY SYSTEMS; ENERGY TRANSFER; HEAT TRANSFER; LIQUID METAL COOLED REACTORS; MASS TRANSFER; REACTOR ACCIDENTS; REACTORS; REMOVAL
Optional Information
- Notes
- 2 refs.; Available on CD-ROM from American Nuclear Society - ANS, 555 North Kensington Avenue, La Grange Park, IL 60526 (US)