Development of method for detecting signs deterioration in insulator of high-voltage motors. 2. Test Results of a new on-line partial discharge monitor for high-voltage motors in nuclear power stations

  • 1. Institute of Nuclear Technology, Institute of Nuclear Safety System, Inc., Mihama, Fukui (Japan)
  • 2. Advanced Technology R and D Center, Mitsubishi Electric Corp., Amagasaki, Hyogo (Japan)
  • 3. Mitsubishi Electric Corp., Tokyo (Japan)

Description

For the purpose of early detection of deterioration of insulators in high-voltage motors which are widely utilized in nuclear power stations, a new on-line partial discharge (PD) monitor was developed and was tested for sixteen motors which were practically running in nuclear power stations. From the test results, it is seen that (1) good signal to noise ratio is obtained by adopting a two frequency correlation method, (2) a resistance temperature detector (RTD) in a motor has sufficient sensitivity to detect PD, (3) when RTD is not installed or is unable to use for this purpose, a radio frequency current transformer (RFCT) can be utilized, although its sensitivity is about 1/10 of that of the RTD monitor. Finally we found a good correlation between the results of this on-line method and the conventional off-line method in which the insulator resistance of a concerned motor was measured during its shut-down, and thereby we demonstrated that this method could be applicable to the on-line test of high-voltage motors in nuclear power stations. (author)

Additional details

Publishing Information

Journal Title
INSS Journal
Journal Volume
7
Journal Page Range
p. 231-238
ISSN
1340-4482

Optional Information

Notes
4 refs., 15 figs., 1 tab.