Published February 1983 | Version v1
Report Open

High efficiency particulate air filter experience survey

Creators

Description

Causes and magnitude of HEPA filter changeouts and failures at DOE sites for the years 1977 to 1979 were evaluated. Conclusions inferred from the data follow: HEPA filters have been generally performing the task they were designed for; most changeouts have been made because of filter plugging, preventive maintenance, or precautionary reasons rather than evidence of filter failure; where failures have been experienced, records generally have not been adequate to determine the cause of failure; where cause of failure has been determined, damage attributed to personnel handling and installation has been substantially more prevalent than that from filter environmental exposure. The need for improved personnel training in handling and installation was stressed. Some reduction in filter failure frequency can be achieved by improving the acid and moisture resistance of filters, and providing adequate pretreatment of air prior to HEPA filtration

Files

14783114.pdf

Files (34.1 kB)

Name Size Download all
md5:6a3c954fd5c281a67ec33bf1ddd1feb5
34.1 kB Preview Download

Additional details

Publishing Information

Imprint Title
Pacific Northwest Laboratory annual report for 1982 to the DOE Office of the Assistant Secretary for Environmental Protection, Safety and Emergency Preparedness. Part 5. Environmental and occupational protection, assessment, and engineering
Journal Page Range
28 p.
Report number
PNL--4600-Pt.5