Field measurements and interpretation of TMI-2 instrumentation: NI-AMP-2

Description

Based on the limited measurements and the attempts to activate the high voltage power supply, the Source Range Monitor which includes NI-AMP-2 is not operating. Since there appears to be an excessive load on the high voltage, it appears that either the detector or cable is defective. However, TDR measurements did not indicate a significant problem with the cable using low level test signals

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS., PC A03/MF A01 as DE82013782.

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Pagination
45 p.
Report number
GEND-INF--017-Vol.11