Published 2016 | Version v1
Miscellaneous Open

Study on the Extremely Low Frequency (ELF) Electromagnetic Field (EMF) emission from overhead High-Voltage Transmission Lines

  • 1. Malaysian Nuclear Agency, Bangi, Kajang, Selangor (Malaysia), Radiation Safety and Health Div.

Description

The paper highlights the study on the Extremely Low Frequency (ELF) Electromagnetic Field (EMF) emission performed at an overhead 275-kV High-Voltage Transmission Lines. The study comprised of assessment at the transmission lines on 3 different cases and locations in Klang Valley, specifically on a vacant land near the transmission line, inside and around the house at the vicinity of the transmission line and the area directly under the transmission line. The instrument setup and measurement protocols during the assessment were adopted from standard measurement method and procedures stipulated under the Institute of Electrical and Electronics Engineers (IEEE) Standard. The results were compared with the standards recommended in the International Commission on Non-Ionizing Radiation Protection (ICNIRP) guidelines. The results showed that the measured field strengths are within the safety limit with the highest measured exposure was 10.8 % and 1.8 % of the permissible exposure limit for the electric and magnetic field respectively. Both the field strengths were found to drop significantly against distance from the transmission lines where closer distances showed higher field strengths. Furthermore, the study revealed that buildings and other object such as trees and shrubs screen out the electric field, resulting in a lower value at indoor measurements and near the stated objects. In addition, higher value of electric and magnetic field strengths were recorded when assessment was being done directly under the transmission line compared to the lateral measurement. (author)

Availability note (English)

Also available in Malaysian Nuclear Agency Document Delivery Center by email: mohdhafizal@nuclearmalaysia.gov.my

Files

48050424.pdf

Files (818.8 kB)

Name Size Download all
md5:c00ef0cd8a454d69c32ea6a6468fd739
818.8 kB Preview Download

Additional details

Publishing Information

Imprint Pagination
9 p.
Report number
INIS-MY--2017-070

Conference

Title
Research and Development Seminar 2016
Acronym
R&D Seminar 2016
Dates
8-10 Nov 2016
Place
Bangi (Malaysia)

INIS

Country of Publication
Malaysia
Country of Input or Organization
Malaysia
INIS RN
48050424
Subject category
S24: POWER TRANSMISSION AND DISTRIBUTION;
Resource subtype / Literary indicator
Conference
Descriptors DEI
ELECTRIC POTENTIAL; ELECTROMAGNETIC FIELDS; FREQUENCY ANALYSIS; FREQUENCY CONTROL; FREQUENCY MEASUREMENT; MALAYSIA; MINT
Descriptors DEC
ASIA; CONTROL; DEVELOPING COUNTRIES; MALAYSIAN ORGANIZATIONS; NATIONAL ORGANIZATIONS

Optional Information

Notes
Oral presentation