Published 1998 | Version v1
Report Restricted

MOV motor and gearbox performance under design basis loads

  • 1. Lockheed Martin Idaho Technologies Co., Idaho Falls, ID (United States). Idaho National Engineering and Environmental Lab.
  • 2. Nuclear Regulatory Commission (United States)

Description

This paper describes the results of valve testing sponsored by the US Nuclear Regulatory Commission, Office of Nuclear Regulatory Research and conducted at the Idaho National Engineering and Environmental Laboratory. The research objective was to evaluate the capabilities of specific actuator motor and gearbox assemblies under various design basis loading conditions. The testing was performed using the motor-operated valve load simulator, a test fixture that simulates the stem load profiles a valve actuator would experience when closing a valve against flow and pressure loadings. The authors tested five typical motors (four ac motors and one dc motor) with three gearbox assemblies at conditions a motor might experience in a power plant, including such off-normal conditions as operation at high temperature and reduced voltage. The authors also determined the efficiency of the actuator gearbox. The testing produced the following significant results: all five motors operated at or above their rated torque during tests at full voltage and ambient temperature; for all five motors (dc as well as ac), the actual torque loss due to voltage degradation was greater than the torque loss predicted using common methods; startup torques in locked rotor tests compared well with stall torques in dynamometer-type tests; the methods commonly used to predict torque losses due to elevated operating temperatures sometimes bounded the actual losses, but not in all cases; the greatest discrepancy involved the prediction for the dc motor; running efficiencies published by the manufacturer for actuator gearboxes were higher than the actual efficiencies determined from testing, in some instances, the published pullout efficiencies were also higher than the actual values; operation of the gearbox at elevated temperature did not affect the operating efficiency

Availability note (English)

Available from INIS in electronic form; ALSO AVAILABLE FROM OSTI AS TI98054121; NTIS; INIS

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Pagination
23 p.
Report number
INEEL/CON--98-00378

Conference

Title
5. Nuclear Regulatory Commission/American Society of Mechanical Engineers symposium on pump and valve testing
Dates
20-23 Jul 1998
Place
Washington, DC (United States)

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
29064339
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
DESIGN BASIS ACCIDENTS; ELECTRIC MOTORS; GEARS; PERFORMANCE; REACTOR COOLING SYSTEMS; VALVES
Descriptors DEC
ACCIDENTS; CONTROL EQUIPMENT; COOLING SYSTEMS; ELECTRICAL EQUIPMENT; EQUIPMENT; FLOW REGULATORS; MACHINE PARTS; MOTORS; REACTOR ACCIDENTS; REACTOR COMPONENTS

Optional Information

Contract/Grant/Project number
Contract AC07-94ID13223
Funding organization
Nuclear Regulatory Commission, Washington, DC (United States)
Secondary number(s)
CONF-980732--