Published November 1988 | Version v1
Journal article

Calculations of condensed moisture escape from a NPP spray pond

Description

A method for calculating water losses due to condensed moisture escape with a wind away from a spray pond used for cooling steam turbine condensator water and emergency nuclear reactor cooling is developed. The method is based on solving a three-dimensional equation of single drop motion, assuming that during the whole flight only gravity and aerodynamic resistance forces act on a drop. The basic parameter variation ranges are the following: 0-18 m/s wind velocity, 0.04-0.12 MPa pressure drop at the nozzle output, 1-2 m height of sprayers above the pond mirror. The given method permits to determine both the amount of circulation water loss and the local liquid flow rate distribution pattern as well as the area around the pond receiving the escaped moisture that is necessary for estimating the ecological situation near a NPP

Additional details

Additional titles

Original title (Russian)
Расчет выноса капельной влаги ис брызгального бассейна AEhS

Publishing Information

Journal Title
Izvestiya Akademii Nauk SSSR, Ehnergetika i Transport
Journal Issue
no.6
Series
Izv. Akad. Nauk SSSR, Ehnerg. Transp.
ISSN
0002-3310
CODEN
IAETA