Test data and operation data from carbon used in high velocity systems

Creators

  • 1. Charcoal Service Corporation, Bath, NC

Description

A 10 CFR 100 review required a utility to change the air flow capacity of its Auxiliary Building Exhaust Filter systems. Since there was not room to increase the size of the system, the system had to be rated at a higher air flow capacity. This changed the residence time of the air in the carbon bed from 1/4 second to 1/8 second. Carbon, to meet these new requirements, had to be tested in the new tech sec mode, and the new tech specs implemented. The results of the testing and the implementation showed that new carbon will meet the requirements, but that the carbon will have a very limited life

Additional details

Publishing Information

Imprint Title
18th DOE nuclear airborne waste management and air cleaning conference: proceedings. Volume 2
Journal Page Range
p. 1436-1440.
Report number
CONF-840806--Vol.2

Conference

Title
18. DOE nuclear airborne waste management and air cleaning conference.
Dates
13-16 Aug 1984.
Place
Baltimore, MD (USA).

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
20023110
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
AIR CLEANING; AIR FILTERS; CARBON; POWER REACTORS; REGULATIONS; SPECIFICATIONS; TESTING
Descriptors DEC
CLEANING; ELEMENTS; EQUIPMENT; FILTERS; LAW; NONMETALS; POLLUTION CONTROL EQUIPMENT; REACTORS