Description
Operating a hybrid HVac and HVdc line is an option for increasing the efficiency of power transmission and overcoming the difficulties in obtaining a new right-of-way. This paper proposes a new calculation method for the study of hybrid line corona. The proposed method can be used to calculate dc corona losses and corona currents in dc or ac conductors for single phase ac and monopolar dc hybrid lines. Profiles of electric field strength and ion current density at ground level can be estimated. The effects of the presence of an energized ac conductor on dc conductor corona and dc voltage on ac conductor corona are included in the method. Full-scale and reduced-scale experiments were utilized to investigate the hybrid line corona effects. Verification of the proposed calculation method is given
Additional details
Publishing Information
- Journal Title
- IEEE Transactions on Power Delivery
- Journal Volume
- 11
- Journal Issue
- 3
- Journal Page Range
- p. 1454-1463.
- ISSN
- 0885-8977
- CODEN
- ITPDE5
Conference
- Title
- 1995 IEEE Power Engineering Society summer meeting.
- Dates
- 23-27 Jul 1995.
- Place
- Portland, OR (United States).
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 28001050
- Subject category
- S24: POWER TRANSMISSION AND DISTRIBUTION;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- CALCULATION METHODS; CORONA DISCHARGES; HVAC SYSTEMS; HVDC SYSTEMS; HYBRID SYSTEMS; POWER LOSSES
- Descriptors DEC
- AC SYSTEMS; DC SYSTEMS; ELECTRIC DISCHARGES; POWER SYSTEMS