New approach for control rod position indication system for light water power reactor
Creators
- 1. Control Instrumentation Division, Bhabha Atomic Research Centre, Mumbai (India)
- 2. Seismology Division, Bhabha Atomic Research Centre, Mumbai (India)
- 3. BARC Safety Council, Bhabha Atomic Research Centre, Mumbai (India)
Description
Control rod position indication system is an important system in a nuclear power plant to monitor and display control rod position in all regimes of reactor operation. A new approach to design a control rod position indication system for sensing absolute position of control rod in Light Water Power Reactor has been undertaken. The proposed system employs an inductive type, hybrid measurement strategy providing both analog position as well as digital zone indication with built-in temperature compensation. The new design approach meets single failure criterion through redundancy in design without sacrificing measurement resolution. It also provides diversity in measurement technique by indirect position sensing based on analysis of drive coil current signature. Prototype development and qualification at room temperature of the control rod position indication system (CRPIS) has been demonstrated. The article presents the design philosophy of control rod position indication system, the new measurement strategy for sensing absolute position of control rod, position estimation algorithm for both direct and indirect sensing and a brief account associated processing electronics. (author)
Additional details
Publishing Information
- Journal Title
- BARC Newsletter
- Journal Issue
- no.347
- Journal Page Range
- p. 3-11
- ISSN
- 0976-2108
INIS
- Country of Publication
- India
- Country of Input or Organization
- India
- INIS RN
- 47015564
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- CONTROL ELEMENTS; DESIGN; DISPLACEMENT GAGES; PERFORMANCE TESTING; REACTOR OPERATION; WATER COOLED REACTORS
- Descriptors DEC
- MEASURING INSTRUMENTS; OPERATION; REACTOR COMPONENTS; REACTORS; TESTING
Optional Information
- Notes
- 7 refs., 11 figs., 2 tabs.