Published 1989 | Version v1
Journal article

Operating experience review of service water system problems

Creators

Description

In a recent paper, selected results of a comprehensive review and evaluation of service water system problems conducted by the Office for Analysis and Evaluation of Operational Data (AEOD) of the US Nuclear Regulatory Commission (NRC) were presented. The results of this review and evaluation indicated that service water system problems have significant safety implications. These system problems are attributable to a great variety of causes and have adverse impacts on a large number of safety-related systems and components. To provide additional feedback of operating experience, this paper presents an overview of the dominant mechanisms leading to service water system degradations and failures. The failures and degradations of service water systems observed in the 276 operating events are grouped into six general categories. The six general categories are (1) fouling due to various mechanisms, (2) single-failure and other design deficiencies, (3) flooding, (4) equipment failures, (5) personnel and procedural errors, and (6) seismic deficiencies

Additional details

Publishing Information

Journal Title
Transactions of the American Nuclear Society
Journal Volume
60
Series
Trans. Am. Nucl. Soc.
Journal Page Range
455-456
ISSN
0003-018X
CODEN
TANSA

Conference

Title
Winter meeting of the American Nuclear Society (ANS) and nuclear power and technology exhibit.
Dates
26-30 Nov 1989.
Place
San Francisco, CA (USA).

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
22012542
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference
Descriptors DEI
AUXILIARY WATER SYSTEMS; ERRORS; FAILURES; FOULING; NUCLEAR POWER PLANTS; REACTOR OPERATION; REACTOR OPERATORS; REACTOR SAFETY; RELIABILITY; SAFETY ENGINEERING; SEISMIC EFFECTS; US NRC
Descriptors DEC
AUXILIARY SYSTEMS; NATIONAL ORGANIZATIONS; NUCLEAR FACILITIES; OPERATION; PERSONNEL; POWER PLANTS; SAFETY; THERMAL POWER PLANTS; US ORGANIZATIONS

Optional Information

Secondary number(s)
CONF-891103--.