AbstractAbstract
[en] An exposure fire test at Sandia Laboratories showed that the Regulatory Guide 1.75 separation guidelines and IEEE-383 fire retardancy standards for safety cables are not sufficient, in themselves, to protect against such fires. Additional measures have been required by NRC to protect essential safety systems against the effects of fires. Two of these measures are fire barriers or fire-retardant coatings on cabling. The report describes the second phase of a small scale and full scale testing program which has been undertaken to assess the adequacy of coatings. In addition, full scale tests are described using exposure fires to appraise the adequacy of some fire barriers placed between horizontal cable trays. The preliminary results show that all coatings and barriers offer some measure of additional protection. Their relative effectiveness is demonstrated by quantitative information obtained in the donor and donee cable trays. An evaluation of other protective measures will be undertaken in future studies
Primary Subject
Secondary Subject
Source
Aug 1978; 87 p; SAND--78-1456; Available from NTIS., PC A05/MF A01
Record Type
Report
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume