Hesboel, R.; Persson, M.
Studsvik Energiteknik AB, Nykoeping (Sweden)1980
Studsvik Energiteknik AB, Nykoeping (Sweden)1980
AbstractAbstract
[en] Iodine filter installations at nuclear power plants are systematically tested regarding light assembly and retention of iodine. Studsvik Energiteknik AB has collected a sizeable amount of test data over the years. The filter installations and test methods are described, followed by an analysis of test results and experience over the past 10 years. As a rule in-situ tests have been carried out at low relative humidity, in 90% of them below 50% relative humidity. Variations in flow have been larger than expected, and the variations in operative conditions affect test results. The test method is, however, regarded acceptable for off-gas filter systems. Additional test methods are required for the auxiliary and energency systems. (G.B.)
Original Title
Resultatsammanstaellning paa in-situ prov av filtersystem i kaernkraftverk
Primary Subject
Secondary Subject
Source
Apr 1980; 28 p
Record Type
Report
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume
INIS IssueINIS Issue