Filters
Results 1 - 1 of 1
Results 1 - 1 of 1.
Search took: 0.018 seconds
AbstractAbstract
[en] A survey of high efficiency particulate air (HEPA) filter applications and experience at Department of Energy (DOE) sites was conducted to provide an overview of the reasons and magnitude of HEPA filter changeouts and failures. Results indicated that approximately 58% of the filters surveyed were changed out in the three year study period, and some 18% of all filters were changed out more than once. Most changeouts (63%) were due to the existence of a high pressure drop across the filter, indicative of filter plugging. Other reasons for changeout included leak-test failure (15%), preventive maintenance service life limit (13%), suspected damage (5%) and radiation buildup (4%). Filter failures occurred with approximately 12% of all installed filters. Of these failures, most (64%) occurred for unknown or unreported reasons. Handling or installation damage accounted for an additional 19% of reported failures. Media ruptures, filter-frame failures and seal failures each accounted for approximately 5 to 6% of the reported failures
Primary Subject
Secondary Subject
Source
Jul 1982; 11 p; 17. DOE nuclear air cleaning conference; Denver, CO (USA); 1 Aug - 6 Sep 1982; CONF-820833--18; Available from NTIS, PC A02/MF A01 as DE83002713
Record Type
Report
Literature Type
Conference; Numerical Data
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume
INIS IssueINIS Issue