Bergman, W.; Kuhl, W.D.; Biermann, A.H.; Johnson, J.S.; Lum, B.Y.
17th DOE nuclear air cleaning conference: proceedings. Volume 11983
17th DOE nuclear air cleaning conference: proceedings. Volume 11983
AbstractAbstract
[en] Two prototype electrofibrous filters were designed, built and evaluated in laboratory tests and in field installations. These prototypes were designed for use in nuclear ventilation ducts as prefilters to HEPA filters. One prototype is designed to be a permanent component of the ventilation system while the other is a disposable unit. The disposable electrofibrous prefilter was installed in the exhaust stream of a glove box in which barrels of uranium turnings are burned. Preliminary tests show the disposable prefilter is effectively prolonging the HEPA filter life
Primary Subject
Source
First, M.W. (ed.); Harvard Univ., Boston, MA (USA). Harvard Air Cleaning Lab; p. 548-575; Feb 1983; p. 548-575; 17. DOE nuclear air cleaning conference; Denver, CO (USA); 1-6 Aug 1982; Available from NTIS, PC A99/MF A01; 1 as DE83009768
Record Type
Report
Literature Type
Conference
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume