[en] Corbicula sp. foul the service water systems at nuclear power plants because the environment within these systems is compatible with the ecological requirements of the species. To reduce Corbicula fouling, components of service water systems and operating procedures that enhance the potential for fouling need to be identified. Factors important in mediating biofouling of service water systems appear to be screening potential, minimum and maximum velocities and the operational procedures employed during power plant biofoulant control and downtime. These conclusions are based on the results of a categorical model we used to correlate information from power plants with that on Corbicula life history. Power plant parameters in the model include temperature, dissolved oxygen concentration, screen and strainer size, maximum and minimum velocities, and elements of the biofouling control procedures. Parameters for Corbicula include tolerances to temperature, dissolved oxygen, biofouling control chemicals, velocity preferences, and optimal temperatures for each life stage and behavior. 13 references, 5 figures