[en] CUTLASS is the CEBG's standard real-time software system for power station applications. It is arranged as four distinct, user orientated languages, any combination of which can be used for a particular application: a DDC language, a Sequence language, a VDU language, and a General Purpose language. All of these languages are supported by a set of Common Language Components. These provide all the standard high-level software facilities - arithmetic and logical manipulation, If statements, For Loops, Sub-Routines, etc.; also in the CLC are high-level statements through which CUTLASS code communicates with proprietary Input/Output hardware. The Common Language Components do not constitute a separate, usable language, so the General Purpose language is often used as a medium for utilizing the facilities provided by the CLC. The DDC language is discussed
Primary Subject
Source
Divakaruni, S.M.; Electric Power Research Inst., Palo Alto, CA (USA). Safety Control and Testing Program; p. 7.3-7.14; Sep 1986; p. 7.3-7.14; Seminar on power plant digital control and fault-tolerant microcomputers; Scottsdale, AZ (USA); 9-12 Apr 1986; Research Reports Center, Box 50490, Palo Alto, CA 94303