Higgins, J.C.; Ruger, C.J.; MacDougall, E.A.; Huszagh, D.
Nuclear Regulatory Commission, Washington, DC (USA). Office of Nuclear Regulatory Research; Brookhaven National Lab., Upton, NY (USA)1988
Nuclear Regulatory Commission, Washington, DC (USA). Office of Nuclear Regulatory Research; Brookhaven National Lab., Upton, NY (USA)1988
AbstractAbstract
[en] Bulletin 85-03 is entitled Motor-Operated Valve (MOV) Common Mode Failures During Plant Transients Due to Improper Switch Settings. The Bulletin requires that NRC licensees implement a detailed program to ensure that MOV operator switch settings are set properly in two particular safety-related systems per operating nuclear power plant. The proposal analyzed herein requires licensees to extend this detailed program to ensure proper MOV switch settings for all safety-related MOVs. A Value-Impact Analysis was performed, according to the guidelines in NUREG/CR-3568, ''A Handbook for Value-Impact Assessment,'' to determine the cost effectiveness of extending NRC Bulletin 85-03, consistent with providing protection of the public health and safety, to cover all safety-related MOVs. The results show that both a very favorable dose aversion and dollar savings can be realized if the proposed actions are implemented. Also, the proposed actions can be justified based on existing requirements. 37 refs., 5 figs., 12 tabs
Primary Subject
Secondary Subject
Source
Jul 1988; 94 p; BNL-NUREG--52145; NTIS, PC A05/MF A01 - US Govt. Printing Office. as TI89002936
Record Type
Report
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume
INIS IssueINIS Issue