[en] On April 14, 1985, the Westinghouse Nuclear Services Integration Division (NSID) issued Technical Bulletin No. NSID-TB-85-17 advising their customers of a potential malfunction in Westinghouse Type DS Class 1E circuit breakers because of broken spring release latch levers. These electrically operated type DS breakers will not close electrically when the spring release latch lever has been broken off. Twenty-five broken levers have been reported and evaluated. This evaluation shows concentrations of incidents traceable to manufacturing in the following periods of time: early 1975, April 1976, and early 1978. This circuit breaker failure, as discussed, adversely affects the safety function (closing on demand) when the circuit breaker is used in the Engineered Safety Features Systems. However, this failure mode will not affect the safety trip function when it is used in the reactor protection system