[en] This information notice is intended to alert addressees to potential safety concerns that may result from failures of GE vertical lift (AM) and horizontal draw-out (AMH) Magne-Blast circuit breakers utilizing ML-13 operating mechanisms to open or close them and AK circuit breakers. The particular breaker failures reported herein were caused by operating problems with prop springs, snap rings and lubricating grease. GE Nuclear Energy has informed the NRC that it is aware of these problems and that GE routinely checks and corrects them if the circuit breakers are serviced at one of the four GE nuclear service centers in the US. However, the NRC is aware that some utilities may have their circuit breakers repaired or serviced at facilities other than the four GE nuclear service centers