[en] The TFTR toroidal field coils, ohmic heating, hybrid and equilibrium field coils are cooled by water from the machine area cooling water system. The system has the following major equipment and capacities: flow rate of 3600 gpm; ballast tank volume of 5500 gal; pumps of 70.4 m head; chiller refrigeration rating of 3300 tons and connecting pipe of 45.7 cm I.D. The performance of the closed loop system was analyzed and found to be adequate for the thermal loads. The field coils were analyzed with detailed thermal and hydraulic models, including a simulation of the complete water cooling loop. Under the nominal operating mode of one second of toroidal field flat top time and 300 seconds of pulse cycle time, the maximum temperature for the TF coils is 530C; for the OH coils 460C and for the EF coils 390C, which are well below the coil design limit of 1200C. The maximum TF coil coolant temperature is 330C which is below the coolant design limit of 1000C. The overall pressure loss of the system is below 6.89 x 105 Pa (100 psi). With the given chiller refrigeration capacity, the TF coils can be operated to yield up to 4 seconds of flat top time. The TF coils can be operated on a steady state basis at up to 20% of the pulsed duty design current rating of 7.32 kA/coil
Primary Subject
Source
Oct 1975; 44 p; Available from NTIS., PC A03/MF A01
Record Type
Report
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume
INIS IssueINIS Issue