Filters
Results 1 - 1 of 1
Results 1 - 1 of 1.
Search took: 0.022 seconds
Fairbrother, D.B.; Lesniak, L.M.; Orgera, E.G.
Babcock and Wilcox Co., Lynchburg, Va. (USA). Nuclear Power Generation Div1977
Babcock and Wilcox Co., Lynchburg, Va. (USA). Nuclear Power Generation Div1977
AbstractAbstract
[en] The report describes the reactor protection system (RPS-II) designed for use on Babcock and Wilcox 145-, later 177-, and 205-fuel assembly pressurized water reactors. In this system, relays in the trip logic have been replaced by solid state devices. A calculating module for the low DNBR, pump status, and offset trip functions has replaced the overpower trip (based on flow and imbalance), the power/RC pump trip, and the variable low-pressure trip. Included is a description of the changes from the present Oconee-type reactor protection system (RPS-I), a functional and hardware description of the calculating module, a description of the software programmed in the calculating module, and a discussion of the qualification program conducted to ensure that the degree of protection provided by RPS-II is not less than that provided by previously licensed systems supplied by B and W
Original Title
PWR
Primary Subject
Source
Oct 1977; 190 p; Babcock and Wilcox, Lynchburg, VA
Record Type
Report
Report Number
Country of publication
Reference NumberReference Number
INIS VolumeINIS Volume
INIS IssueINIS Issue